Voltage and frequency protection

Voltage and frequency protection in 1 or 3 phase photovoltaic systems

Functions

  • Voltage and frequency protection in 1 or 3 phase photovoltaic system
  • Simple, fast and reliable setting of parameters thanks to a rotary encoder with a built-in button
  • Full color screen allows the device show settings and statistics at a glance
  • Pre-set profiles from the major electricity distributors as well as the ability to configure voltage and frequency protection levels and shut-down times yourself
  • Password protected settings
  • Partial screen darkening for lower power usage. If a defect is detected, the screen will set itself to full brightness
  • Input for remote control of connecting FV system by connecting N from a HDO system receiver
  • 3 built-in 16A/250V power relays. No need for an external solution
  • Built-in helper relays for remotely displaying or indicating connection state of FV system
  • 100–277VAC supply voltage, power consumption under 5W
  • Single phase measurement range: 100–295VAC, 3 Phase: 170–520VAC
  • Option of 1–3 degrees of protection

Technical specifications

  • Supply voltage 100–277VAC, 45–65Hz, power consumption < 5W
  • Range of measured ULN voltage: 100–295VAC, ULL: 170–520VAC
  • Precision ± 0.5%, range 100VAC– 290VAC RMS
  • Measuring L1, N frequency: 41.67–65Hz ±0,5%
  • Uncertainty of measurement 0.4%, 64000 samples per 50hz period at every measuring input
  • Power supply terminals L1, N
  • Measurement terminals L1, L2, L3
  • Input impedance of measuring input L1, L2, L3: 940k Ohm
  • Switching terminals L1’, L2’, L3’ galvanically separated from L1, L2, L3
  • 3 degrees of protection, single or 3 phase
  • Configurable switching delay: 1–50 minutes (while testing in service mode with accelerated switching)
  • Power switching relays
    • AgSnO2 contacts
    • Constant resistive load 16A/250VAC
    • Maximum switching power per contact 4000VA
    • Maximum switching current per contact 25AAC
    • Mechanical endurance 2×106
    • Electrical endurance 20A/250VAC (cos ϕ=1)
  • Auxiliary switching relay
    • AgSnO2 contacts
    • Constant resistive load 6A/250VAC, 24VDC
    • Maximun swithing power 1505VA/144W
    • Maximum switching power 100mA/5VDC
  • Operating temeperature –20°C up to +50°C
  • Storage temperature –30°C up to +70°C, air humidity up to 90% (non-condensing)
  • IP20 protection
  • Overvoltage category III
  • Dielectric strength 4kV, 4kV burst resistance, 2.5kV surge on all inputs in accordance to STN-EN 61000–6–2
  • Working position vertical on DIN rail
  • Cross section of connecting wires:

    Power relay terminals: solid wire 6mm2 wire with 4mm2 crimp end.

    Other terminals: solid wire 2.5mm2 wire with crimp end 1.5mm2

  • DIN rail mounting
  • Dimensions of 6 modules, 105×90×75mm

Norms and laws

Zhoda: zákon 56/2018 Zz
Metrológia: STN EN 61000–4–30
Ochrany: STN EN 50549–1, STN EN 60255–1
Bezpečnosť: STN-EN 61010–2–201, STN EN 60664–3
EMC: 127/2016 Zz, 331/2019 Zz, STN EN 61000–1–2, STN EN 61000–6–1, STN EN 61000–6–3, STN EN 1000–3–2

Technický list (8,2 MB)